Pollution flashover, ice flashover, rain flashover, and lightning strikes are the most harmful to the external insulation of the power system. Although the number of lightning strikes accounts for the first number of external insulation accidents, the loss of pollution flashover is nearly 10 times that of lightning strikes. As early as 1907, a pollution flashover accident occurred on a 25kV AC transmission line near the coast of Italy. By the 1950s, the pollution flashover accidents in various countries in the world had become very serious. 0.6 times/(100km a); 162 pollution flashover accidents occurred in Japan in 1961; more than 400 pollution flashover accidents occurred on 50-400kV lines in Scandinavia in 1969; pollution flashover accidents occurred on 60--150kV lines in Denmark The tripping rate of the accident is 1-4.3 times/(100km·a); in 1960"-"1970 in the industrial and coastal polluted areas of the United States and Canada, a large number of pollution flashover accidents occurred in the 12-500kV power grid. The eastern coast of my country Pollution flashover accidents occurred in industrially developed areas in the 1950s. In the 1960s, pollution flashover accidents gradually spread to various power grids across the country, not only in industrial cities and coastal areas, but also in rural and inland areas. Pollution flashovers have become increasingly widespread and frequent The daily high and the increasing losses have seriously restricted the economic development and the improvement of people's living standards.
Commonly used test methods can be divided into constant voltage method and uniform boost method according to the voltage application method during the test process, and can be divided into salt spray method, solid layer method and wet pollution method according to the difference in insulator contamination and wet process. The constant voltage method is a pressurization method that quickly raises the voltage to the expected test voltage and keeps it constant for at least several minutes. This pressurization method is consistent with the working state of the dirty insulators running in the system, and the test dispersion is small, but the test period is long. It is the method recommended by IEC and national standards. The boost method is not a method recommended by the standard, but a method commonly used in scientific research is to increase the applied voltage uniformly at a certain speed until the test product flashes over. The boost method does not have this kind of operation in the power system, but the cycle of this test method is very short, and a large amount of test data can be obtained in a short period of time. It is especially suitable for various research tests and comparative tests, so it is obtained widely used. The wet pollution method is not a method recommended by the standard. Since the test process does not require artificial spraying, there is no need to build an artificial fog chamber. It is simple and easy to implement, and is especially suitable for artificial pollution tests of long strings of insulators and large-sized insulators in ultra-high voltage systems.
According to the research status of pollution flashover at home and abroad, the constant voltage test is to keep the voltage applied to the sample constant throughout the test process. Under these conditions, the formation process of pollution flashover is observed, which is usually used to simulate the pollution flashover of insulators in actual operation (under constant voltage). Boost test is in the test process. The voltage is gradually applied to the sample. It is mainly used to understand the relationship between pollution flashover occurrence and voltage. Obtain the withstand voltage, critical voltage or 50% flashover voltage of the test sample under the polluted condition. It is generally believed that the boost test method is often used when calculating the average value of the insulator flashover voltage or the 50% flashover voltage, and the constant voltage test is often used when calculating the maximum withstand voltage or 50% withstand voltage of the insulator.